Technical Data of PV Cable:
Material code |
Cross section (mm) |
Conductor construction (nmm) |
Cable OD. (m) |
Conductor Max. Resistance AT 20c (Qkm) |
current carryng capacity AT6o ) |
Reference weight (kgl/km) |
EP25001001 | 2.5 | 45/0.25 | 5.9o | 8.21 | 41 | 51.66 |
EP40001011 | 4 | 56/0.28 | 6.3 | 5.09 | 55 | 67.41 |
EP60001001 | 6 | 78/0.295 | 7 | 3.39 | 70 | 90.15 |
EPA1001001 | 10 | 7710.4 | 8.6 | 1.95 | 98 | 145.45 |
ADVANTAGES
Electron-beam cross-linked material
Good flexibility
Good low temperature resistant
Good high temperature resistant
Weather/UV resistant
Acid and alkaline resistant
Ozone resistant
Damp heat resistant
Long application life:More than 25 years
CONSTRUCTION
Conductor:Soft tinned annealed copper according to IEC 60228 class 5
lnsulation:XLPE,Halogen free
Jacket:XLPE,Halogen free
Electrical performance
Rated voltage:UO/U=1000/1000V 1500VDC
U=1000v or 2000v
Test voltage:AC 6.5KV or DC 15KV,5Min.Thermal performance-
Ambient temperature:-40℃~+90℃
Max.Temperature at conductor:120℃
Max. short circuit temperature:250℃,5s
Material properties/Standard
Flammability: EN60332-1-2;UL2556 vw-1
Smoke emission:EN61034-2
Weathering/UV-resistance:EN50618 Annex E;UL2556O-zone resistance:EN50396;UL2556
Applied standard:EN50618;UL4703